Cable Sizing Calculator
Calculate minimum cable size based on load current, installation method, derating factors, and voltage drop requirements.
For reference only — always verify with the current published standard and consult a licensed electrical engineer for critical installations.
Cable Parameters
Load
Cable
Installation
Environment
About This Cable Sizing Calculator
This calculator determines the minimum cable size for a circuit based on load current, installation method, and derating factors. Built for Australian electricians who need a quick reference during design or quoting.
Use it when sizing sub-mains, final sub-circuits, or any cable run where you need to check current capacity and voltage drop together. Enter your load, pick your installation method, and get a result in seconds.
Calculations follow AS/NZS 3008.1.1 current-carrying capacity tables and AS/NZS 3000 voltage drop limits. This is a reference tool only. Always verify results against the current edition of the standard for your specific installation.
It is free with no signup — no locked features, no app to install.
While the cable pulls: RBZ 3D makes custom switchboard labels online — instant pricing, no minimum order.
How Cable Sizing Works Under AS/NZS 3008
Sizing a cable properly means checking it against three separate requirements, and the cable has to pass all three — not just the biggest one.
- Current-carrying capacity. Every cable has a base rating for its conductor size, insulation type, and installation method. That base rating then gets derated for ambient temperature, grouping with other loaded circuits, and contact with thermal insulation, so the conductor stays within its rated operating temperature under real site conditions.
- Voltage drop. Even a cable with plenty of current-carrying capacity can fail on a long run, because voltage lost along the conductor scales with distance and current. AS/NZS 3000 caps total voltage drop at 5% from the point of supply to the load.
- Short-circuit and earth-fault withstand. The cable also has to survive the fault current available at that point in the installation for as long as it takes the upstream protection to clear it, without the conductor or insulation being damaged.
This calculator handles the first two automatically from your load, installation method, and run length, and will run the third if you enter a fault level and clearing time. For a deeper look at how the derating factors stack up, see the cable derating calculator. To check a specific run against the 5% limit on its own, use the voltage drop calculator.
Installation Methods Matter
The same cable carries different current depending on how it is installed, and it is not a small difference. A conductor clipped direct to a wall in open air sheds heat straight into the surrounding air on all sides. Put that same conductor inside conduit, and the heat has to conduct through the conduit wall first, with far less air movement to carry it away. Bury it in the ground, and the surrounding soil is a worse conductor of heat again, plus the fault current path and drying-out effects around the cable come into play.
Because the conductor has to stay under its maximum operating temperature to protect the insulation, a more restrictive installation method means a lower current rating for the same cable size — or a bigger cable to carry the same current. That is why the installation method you select in the calculator above changes the result even when the load and cable type stay identical. Grouping multiple circuits together compounds it further, since bunched cables all competing to dump heat into the same limited space each run hotter than they would on their own.
Worked Example
Say you are feeding a 15kW three-phase motor at 400V with a 0.85 power factor, running 40m of cable enclosed in conduit on a wall, ambient temperature 35°C, sharing that conduit with two other loaded circuits. Before anything else, work out the full load current the cable actually has to carry:
25.5A is the input current, not the answer — it is only the starting point for the current-carrying capacity check. From there, the calculator applies the ambient temperature derating for 35°C, a grouping derating for three circuits sharing the conduit, and then checks the 40m run for voltage drop at that current. Enter these exact assumptions above and it will return the minimum compliant cable size and confirm whether voltage drop clears the 5% limit — worth doing rather than guessing, since the derating and grouping factors together can shift the result by more than one standard cable size compared with a cable in free air.
Earth Conductor Sizing
The earthing conductor does not need to match the active conductor size one-for-one as cables get bigger. AS/NZS 3000 Table 5.1 sets a minimum earth size relative to the active: for smaller circuits the earth typically matches the active size, but once the active gets large enough the table allows the earth to be a smaller fraction of it. That is because the job of the earth conductor during a fault is short-duration — it has to carry fault current only for as long as it takes the protection to trip, not carry full load current continuously the way the active does.
There is a second check that can push the earth size back up: the adiabatic (I²t) calculation, which looks at the actual prospective fault current and how quickly the upstream protection clears it. On sub-mains protected by slower-clearing devices, the adiabatic result can demand a bigger earth than the Table 5.1 minimum. Always check both — the table minimum and the adiabatic result — and use whichever is larger. If you need to verify that your protection actually clears a fault fast enough for the earth size you have chosen, the earth fault loop calculator checks that side of it.
Cable Sizing Calculator FAQs
What size cable do I need for a 32A circuit?
There is no single answer to that on its own — 32A is just the starting current. The minimum cable size also depends on installation method, ambient temperature, how many other circuits it runs alongside, and the run length for voltage drop. A 32A circuit clipped direct on a short run needs a noticeably smaller cable than the same 32A load buried underground over 40m. Enter your actual conditions into the calculator above to get the correct minimum size rather than relying on a rule of thumb.
What is AS/NZS 3008?
AS/NZS 3008.1.1 is the Australian/New Zealand standard for selecting cables in electrical installations up to 0.6/1 kV AC. It sets out current-carrying capacity, voltage drop, and short-circuit temperature rise for common cable types and installation conditions. AS/NZS 3000 (the Wiring Rules) sets the compliance limits — like the 5% voltage drop cap — while AS/NZS 3008 supplies the cable data used to meet them. This calculator applies both together.
Does cable length affect cable size?
Yes, through voltage drop. A cable's current-carrying capacity does not change with length, but the voltage lost along the run does — it scales directly with distance. A short run might be fine at the minimum size for current capacity alone, while the same load over a long run needs a larger cable purely to keep voltage drop within the AS/NZS 3000 limit. This calculator checks both and sizes for whichever requirement is more demanding.
What derating factors apply to cable sizing in Australia?
Cables must be derated for ambient temperatures above 40°C (the reference temperature in AS/NZS 3008), grouping of multiple circuits, thermal insulation contact, and burial depth for underground installations. This calculator applies the correct factors automatically based on your inputs.
What is the maximum voltage drop allowed per AS/NZS 3000?
5% total from the point of supply to the load. Sub-mains are typically limited to 3%, leaving 2% for final sub-circuits. This calculator checks voltage drop using the correct mV/A/m values for your cable size and conductor temperature.
Is this AS3008 cable calculator free to use?
Yes. The calculator is completely free with no signup, no app download, and no usage limits. It runs in the browser on any phone, tablet, or desktop, so you can size a cable on site or at the desk. It is a reference tool — always verify the result against the current edition of AS/NZS 3008.1.1 for your installation.
Related Tools
Need cable labels for your installation? Design and order custom engraved labels online — from $1 ex GST.