Voltage Drop Calculator
Check voltage drop percentage for cable runs against AS/NZS 3000 limits — 3% for sub-mains, 5% for final sub-circuits.
For reference only — always verify with the current published standard and consult a licensed electrical engineer for critical installations.
Voltage Drop Inputs
About This Voltage Drop Calculator
This calculator checks whether your cable run stays within the allowable voltage drop limits. Designed for Australian sparkies sizing sub-mains and final sub-circuits on residential and commercial jobs.
Use it when you know the cable size and need to confirm the voltage drop percentage before pulling cable. Handy for long runs, shed supplies, and any circuit where drop is borderline.
Voltage drop values are based on mV/A/m tables from AS/NZS 3008.1.1 and checked against the 5% total limit in AS/NZS 3000. This is a reference tool. Verify results against the current edition of the standard.
It is free to use with no signup — open it on your phone on site and check a run in seconds.
How Voltage Drop Is Calculated
AS/NZS 3008.1.1 gives every cable size and installation method a millivolt-per-amp-per-metre value — Vc for short. It is a single number that bundles up the cable’s resistance and reactance at operating temperature, so you do not have to calculate impedance from scratch. The values live in AS/NZS 3008.1.1 Table 42 onward, one table per insulation type, conductor material, and installation method.
Once you have Vc, the formula is short:
Where:
- Vd — voltage drop, in volts
- L — one-way cable length, in metres
- I — the load current, in amps
- Vc — the cable’s mV/A/m value from AS/NZS 3008.1.1, matched to conductor size, material, and insulation type
Divide the result by the supply voltage and multiply by 100 to get a percentage — that is what gets checked against the AS/NZS 3000 limit.
Single-phase and three-phase runs use different Vc figures for the same cable size. Single-phase values are worked out over the full active-neutral loop, so they read higher. Three-phase values reflect the balanced line-to-neutral drop and come in lower — typically around 0.866 (√3⁄2) of the single-phase figure for the same conductor. This calculator picks the right value automatically once you set the phase configuration.
The Limits
AS/NZS 3000 Clause 3.6.2 sets a hard limit: total voltage drop from the point of supply to the furthest point of utilisation must not exceed 5% of the nominal supply voltage. That is one budget covering the whole installation — consumer mains, sub-mains, and final sub-circuits added together, not 5% for each section separately. A 7% limit applies only where the point of supply is a dedicated substation on the same premises as the installation, which is not the typical street-fed job.
Since the 5% has to be shared across the whole run, most designers split it up before they start pulling cable. A common approach is to budget around 2% for consumer mains and sub-mains, leaving roughly 3% for final sub-circuits — or the reverse, depending on where the long run sits. This split is a design convention, not a separate clause in the standard. AS/NZS 3000 only cares about the 5% total; how you divide it between sections is a judgement call based on where your longest or most heavily loaded run actually is.
That is why this calculator checks a run against both 3% and 5%: 3% as a sanity check against common design practice for one section of the installation, and 5% as the actual clause limit for the whole run from the point of supply.
Worked Example
Take a 32A single-phase circuit run in 6mm² copper over a 45m route — a fairly typical shed or workshop sub-main. AS/NZS 3008.1.1 gives 6mm² copper (V-75 insulation, single phase) a Vc of 7.50 mV/A/m.
4.70% is under the 5% total limit from AS/NZS 3000, so this run passes on the clause itself. But if this is a sub-main and the mains upstream have already used their share of the budget, 4.70% alone eats almost all of a typical 2%/3% split — worth flagging even though it technically passes. Step up to 10mm² copper and the same run drops to 6.42V, or 2.79% — comfortably inside a 3% sub-main budget with margin left for the final sub-circuit downstream. Run both sizes through the calculator above to see the numbers side by side.
Voltage Rise For Solar
Everything above deals with voltage drop — current flowing from the switchboard out to a load, with the far end of the cable sitting below supply voltage. A solar inverter exporting to the grid runs the same cable the other way: current flows from the inverter back toward the point of supply, and the far end of that cable — at the switchboard — ends up above supply voltage instead of below it. That is voltage rise, and it is what a voltage rise calculator for Australian solar jobs is really checking.
AS/NZS 4777.1 caps voltage rise at 2% of nominal voltage, measured from the point of supply to the inverter’s AC terminals, calculated at the inverter’s rated export current. On a 230V single-phase supply that is roughly 4.6V; on 400V three-phase it works out to around 8V line-to-line.
The maths is identical to the voltage drop formula above — same Vd = (L × I × Vc) / 1000, same mV/A/m tables. The only difference is which current you plug in: instead of a load current, use the inverter’s rated AC output current at full export. Enter the AC cable length from the inverter back to the switchboard, the cable size, and the inverter’s rated current as the load current in the calculator above, then check the result against 2% instead of 5%.
For sizing the DC side of a string, use the solar DC cable sizing calculator instead — DC strings run to AS/NZS 5033, not AS/NZS 4777.1. To check the full installation against CEC and AS/NZS 5033 requirements, see the solar compliance checker.
Labelling the isolators and inverter AC/DC runs while you are at the board: RBZ 3D makes custom electrical labels online — instant pricing, no minimum order.
Voltage Drop Calculator FAQs
What is the maximum voltage drop allowed in Australia?
AS/NZS 3000 Clause 3.6.2 limits total voltage drop to 5% of the nominal supply voltage, measured from the point of supply to the furthest point of utilisation. That 5% covers the whole installation — mains, sub-mains, and final sub-circuits combined, not 5% for each section.
Is voltage drop 5% or 7%?
5% for a standard low voltage installation. AS/NZS 3000 allows a higher 7% limit only where the point of supply is a dedicated substation on the same premises as the installation — for example a large industrial site with its own transformer. For a typical residential or commercial job fed from the street, work to 5%.
How do I calculate voltage drop for a cable run?
Multiply the cable's millivolt-per-amp-per-metre value (from AS/NZS 3008.1.1 tables) by the load current and route length, then divide by 1000 to get volts dropped. Divide that by the supply voltage for the percentage. This calculator does it automatically for copper and aluminium cables, single or three phase.
Does voltage drop change between single phase and three phase?
Yes. Single-phase mV/A/m values are higher than three-phase for the same cable size, because a single-phase circuit's voltage drop is worked out over the full active-neutral loop, while the three-phase value reflects the balanced line-to-neutral drop. As a rough check, the three-phase figure is close to the single-phase figure multiplied by 0.866 (√3⁄2).
How do I reduce voltage drop on a long cable run?
The most effective way is to step up the cable cross-sectional area — going from 4mm² to 6mm² cuts voltage drop by roughly 35% at the same length and current. Other options are shortening the route, running parallel cables to share the load, or reducing the circuit current. AS/NZS 3008.1.1 allows parallel cables of matched size and length as an alternative to one larger conductor. Run a few sizes through this calculator to see which one clears the limit without over-specifying the cable.
What about voltage rise on solar?
Solar export runs the same maths in reverse. Instead of a load pulling current from the switchboard, the inverter pushes current back through the same cable, and the far end sits above supply voltage instead of below it. AS/NZS 4777.1 caps that voltage rise at 2% from the point of supply to the inverter AC terminals, calculated at the inverter's rated export current. Enter the inverter's full-load AC current as the load current in this calculator to check the rise on your AC cable run.
Related Tools
Need cable labels for your installation? Design and order custom engraved labels online — from $1 ex GST.