Voltage Rise Calculator
How far does the voltage climb between the inverter and the point of supply? Enter the export current, the cables and the run.
Data: AS/NZS 3008.1.1:2017 mV/A/m tables, 2025 edition not yet applied. The rise limit is the one you enter. About standard editions
Inverter and cable
1 for most inverters at full export.
Switchboard to the point of supply. 0 to leave out.
Measured at the point of supply. 0 to leave out.
Enter the limit from your copy of AS/NZS 4777.1 or your network's connection requirements.
Voltage rise
Enter your limit above to check the rise against it.
- Export current
- 21.74 A
- Inverter to board: 6 mm², 25 m at 7.5 mV/A/m
- 4.08 V
- Consumer mains: 16 mm², 20 m at 2.81 mV/A/m
- 1.22 V
- Total rise
- 5.3 V
Solar warning labels from $10.59 each.
Engraved traffolyte PV and battery warning signs, made in Townsville, posted Australia wide. Order online.
Design solar labelsLabel the array while the numbers are in front of you.
How Voltage Rise Is Calculated
Voltage rise is voltage drop run backwards. The inverter pushes its export current through the AC cable to the switchboard, then through the consumer mains to the point of supply. Each cable adds a little voltage at the inverter end.
- Vr: voltage rise for that cable section, in volts
- mV/A/m: the cable value from the AS/NZS 3008.1.1:2017 tables, copper, V-75, the same figures the voltage drop tool uses
- I: inverter AC current per phase, in amps
- L: one-way route length, in metres
Add the sections together, then divide by the nominal voltage (230 V single phase, 400 V line to line three phase) and multiply by 100 for the percentage. If you enter the kW rating instead of the current, the tool uses I = P / (V × PF) for single phase and I = P / (√3 × V × PF) for three phase.
The limit is yours to enter. Take it from your copy of AS/NZS 4777.1 or from your network’s connection requirements. The tool only tells you whether the rise is under the number you entered.
Worked Example
A 5 kW single phase inverter at power factor 1 on a 230 V supply. The inverter is 25 m from the switchboard in 6 mm² copper, and the consumer mains run 20 m in 16 mm² copper.
Too high for your limit? Step the inverter cable up to 10 mm² (4.46 mV/A/m). That section drops to 2.42 V and the total to 3.65 V, or 1.59%. The inverter cable is usually the cheapest place to win the volts back.
For voltage drop on load circuits use the voltage drop calculator. Same cable values, same engine.
Questions
- What is voltage rise?
- When a solar inverter exports, current flows from the inverter back out to the grid. The cables have resistance, so the inverter end sits higher than the point of supply. That difference is the voltage rise.
- How do I calculate voltage rise?
- Same formula as voltage drop, with the inverter export current. Vr = mV/A/m x I x L / 1000 for each cable section, then add the sections. Divide by the nominal voltage and multiply by 100 for the percentage.
- What voltage rise limit do I use?
- The one in your copy of AS/NZS 4777.1 and your network's connection rules. This tool does not type a limit in for you. Enter yours and it tells you if the rise is under it.
- Which current do I enter?
- The inverter's rated AC output current per phase, off the datasheet. That is full export, the worst case. If you only have the kW rating, enter that and the tool works out the current.
- Why does an inverter trip on high voltage?
- The inverter sees the street voltage plus the rise in its own cables. If the street is already high and the cables add a few volts, the inverter can reach its over-voltage setting and back off or trip. A bigger AC cable or a shorter run cuts the rise.
What customers say
All reviewsReviews scroll sideways. Swipe, or use the arrow keys or the Next button, to see more.
“As soon as I had put my order in, Josh was on the phone to me to adjust a few things to make sure it was 100% right. Couldn’t ask for better service and transparency from designing all the way to picking up the labels.”
“Great service from RBZ 3D. The ordering process was straightforward, communication was clear, and the finished product met our expectations. Delivery was prompt, and the quality was excellent. We'd happily use RBZ 3D again and recommend them to others.”
“Was so easy to order & to have them personally delivered was great”
“⭐⭐⭐⭐⭐ Absolutely stoked with my order from RBZ 3D! Josh made the name plaques for my LEGO polybag minifigure collection, and the quality is excellent. They look fantastic and really finish off the display. On top of the very fast turnaround, they included 20 extra plaques at no cost! I couldn’t spot a single fault with any of the extras either—an incredibly generous touch that was much appreciated. A huge thank-you to Josh for going above and beyond. Brilliant quality, fast service and a business I’d happily recommend. Five stars well deserved! 🤙”
“This service is great. The designer is extremely flexible, and you can store your own made templates or choose from pre-made templates. Sizes and colours, sticky back or not, it's just what I needed. Also, the label quality is very high. Will be using these guys repeatedly!”
“We are fairly new to Josh, but I cannot fault his prices, service and quick turnaround. He provides high-quality accurate labelling at a very competitive price. Recommended highly.”
“Prompt service, good quality. Main earth and earth bond”
“Great communication, fast turn around and shipping and well packaged. The product is also excellent quality. Will definitely order from here again.”
“Great quality labells as ordered, will order again.”
“QUICK TURNAROUND, VERY PROFESSIONAL AND ACCURATE”
“Everything was easy from ordering to delivery”
“My order was processed quickly and the final product met or exceeded my expectations.”