4-20 mA Signal Scaler

What process value is 12 mA, or what current is 50 kPa? Linear and square root.

Data: No standard tables used. Linear and square-root scaling only. About standard editions

For reference only. Always verify instrument scaling against the manufacturer data sheet and site calibration records.

Signal Scaler Inputs

Linear scaling: standard for pressure, temperature, level

The process variable unit label (display only)

mA

Calibration Reference

5-point table for linear scaling: 0 to 100 kPa

% RangeSignal (mA)PV (kPa)
0%4.0000.000
25%8.00025.000
50%12.00050.000
75%16.00075.000
100%20.000100.000

About 4-20 mA Signals

  • 4 mA = 0% of range (zero / LRV). A live zero allows fault detection: a true 0 mA indicates a broken loop.
  • 20 mA = 100% of range (span / URV).
  • Square root extraction is used with DP (differential pressure) flow transmitters because flow rate is proportional to the square root of differential pressure.
  • NAMUR NE 43 defines signal levels for fault indication: <3.6 mA and >21.0 mA are typically used for diagnostics.