Sparky tools

Thermocouple Converter

Convert millivolts to temperature and back, with cold junction compensation.

Data: Type J checked against NIST Monograph 175 (ITS-90). Other types not yet checked against it. About standard editions

For reference only. Based on IEC 60584 simplified tables with linear interpolation. Always verify against certified reference tables for critical measurements.

Thermocouple Converter

Thermocouple Type

Type K (Chromel / Alumel)|Range: -200°C to 1372°C|-5.891 to 54.886 mV|
Green/White

Conversion Mode

Input Values

Valid range: -5.891 to 54.886 mV

0°C = ice-point reference (ideal). Field conditions often 25°C.

Type K Reference Table

IEC 60584 reference values: Type K (Chromel / Alumel)

Temp (°C)mV
-200-5.891
-150-4.913
-100-3.554
-50-1.889
00.000
502.023
1004.096
1506.138
2008.138
25010.153
30012.209
35014.293
40016.397
45018.516
50020.644
55022.776
60024.905
65027.025
70029.129
75031.213
80033.275
85035.313
90037.326
95039.314
100041.276
105043.211
110045.119
115046.995
120048.838
125050.644
130052.410
137254.886

Standard References

  • IEC 60584-1, Thermocouples: EMF specifications and tolerances
  • AS 1771, Colour coding: AU/NZ thermocouple identification
  • ASTM E230: Standard specification for temperature-EMF tables

Equipment and instrument tags from $3.08 each.

Engraved traffolyte tags with your tag or loop numbers, made in Townsville, posted Australia wide. Order online.

Design equipment tags

Tag the gear while the numbers are in front of you.

Questions

What is cold junction compensation?
A thermocouple measures the difference between the hot junction and the point where its wires meet the instrument, the reference or cold junction. If that point is not at 0 °C, the millivolts read low by the value for that temperature. The tool adds that value back before it converts.
What reference junction temperature do I enter?
The temperature at the terminals where the thermocouple or its extension cable lands, usually the transmitter or the instrument. Leave it at 0 °C for the plain table values.
How accurate is the conversion?
The tool draws a straight line between reference points taken from the IEC 60584 tables. That is good enough to check a reading or a loop. For calibration work, use the full reference tables or your calibrator.
Which thermocouple types does it cover?
Types K, J, T, E, N, R, S and B. Each has its own range, for example Type K from -200 to 1372 °C and Type T from -200 to 400 °C. A value outside the range shows a warning instead of a result.
How do I simulate a temperature with a millivolt source?
Switch to temperature to millivolts and enter the temperature and the reference junction temperature. The compensated figure takes off the reference junction millivolts. That is what an instrument with cold junction compensation expects at its terminals.